Power supply of ETL-35K is possible due to an industrial single-phase network of 220V, 50 Hz.
Power from the independent generator of power supply with the capacity not fewerthan 2,2 kV-A is permitted.
For full options providing of ETL-35K generator capacity should be not fewerthan 20 kV-A.
| 1 Test Block BHT-100 |
The variable voltage of 50 Hz - 50 kV, insulation of a secondary winding 100 kV. The secondary winding is connected to outlet of variable voltage BHT-60, as a result at the output of block BHT-100 the variable voltage of 100 kV is got, total out capacity is 8 kw., a short of 100 kV.
|
| 2 The Insulation Checking Block |
The maximal voltage is 25 kV, the maximal current of short circuit is 40 A, out capacity is 8 kW, the maximal consumed current is 80 A. 6 steps of out voltage
|
| 3 Generator of Acoustic percussion waves GAPW-5 |
The maximal voltage is 20 kV, pulse energy is 2500 J. The operating mode can be manual or automatic. A mode of teamwork with the insulation checking block is provided.
|
| 4 The Control Unit |
Is intended for controlling the test block, insulation checking and rechecking, generator AG -5, measuring instrument IDP-10, measurement of in and out parameters
|
| 5 Acoustic generator AG-2500 with a receiver R-805 |
The maximal voltage is 300 V, the maximal current - 100 A, fine adjustment, signal modulation, 12 stages, two frequencies of 1024 and 2048 Hz. The bandwidth of the receiver is 7 Hz at a level of 0,7. The receiver belongs to the inductive –acoustic type.
|
| 6 High-voltage reflectometer "Iskra" |
It is intended for definition of character of damage and distance up to a place of damage without прожига to isolation ка-bleaching (analogue of device " KABELLUX " of firm SEBA DYNATRONIC)
|
| 7 The Basic Post |
The bearing structure containing an instrument post, drawers, a little table, a locker, etc.
|
| 8 The Set of drums and cables |
Two posts with six drums for KAEL-3: a high-voltage cable of 60 kV. A profile of a conductor and a casing is 4 mm 2 (3 pieces) The length of all the wires and cables is 30 m.
|
| 9 The High-Voltage Switch |
The switch for three directions for connecting with three conductors of a high-voltage cable
|
| 10 Regulator РNО |
Adjustment of voltage of the test block for testing with variable voltage
|
| 11 Measuring instrument IDP-10 |
The measuring instrument of capacity and tangent of dielectric losses of insulation. Consists of the bridge of an alternating current R5026, transformer NOM-10, the sample condenser R5023, the switch of the measuring scheme "straight line-turned”, the device of indemnification of influence currents UKTV-2.
|
| 12 The Set of Shorts |
Contains four shorts with an electromechanical drive for manual or automatic grounding of high-voltage outputs of the electrolaboratory
|
| 13 Measuring instrument ITV-2 |
The measuring instrument of a current leak at high voltage for testing dischargers. Limits of measurement are 100, 300, 3000 mcA.
|
| 14 The Set of Electrotechnical Equipment |
Blockings, a siren, a red lantern, a set for fencing the automobile, a set of posts and stands for putting high-voltage wires, a bushing, a temperature fan, a case for devices, a door to a high-voltage compartment, etc.
|
| 15 Low-Voltage Block BHT |
For measuring parameters of transformers (test КЗ and XX, measurement of ohmic resistance of contacts, etc.) It is applied together with measuring devices of. 0,5 or 0,2 Cl.
|